Page 951 - Plastic Process Equipment, Inc
P. 951
WIRING CONFIGURATIONS
AND DIAGRAMS
These wiring configurations are provided to assist in the wiring of heating elements in parallel, series and 3-phase (Delta or Wye)
LINE 1 LINE 2 LINE 1 LINE 2
i (ELEMENT I (LINE AMPS)
AMPS)
ELEMENT
R R 1 R 2
1
e
R
2 E
PARALLEL One or more elements wired across two line wires. SERIES Two or more elements or equal resistance wired
Element volts equal line volts. Total power is equal to sum of together and across line wires. Element volts equal line volts
watts in each element. Line amps equal sum of current of each divided by number of elements. Total power is equal to sum of
element. watts of elements. Line amps equal current thru each element.
LINE 2 LINE 2
LINE 1 LINE 3
ELEMENT W e R
E
(LINE VOLTS)
WE R
LINE 1 LINE 3
DELTA (3Ø) Three elements or groups of elements wired in a STAR or WYE (3Ø) Three elements or group of elements wired
triangle (Delta). Power is: W = 1.73E x I where E is volts between in a Wye ("Y"). Total power is W = 1.73E x I, where E is volts
any 2 lines and I is current in any 1 line. Power in each side of between any 2 lines and I is current in any 1 line. Volts across
Delta is 1/3 of total. Volts across each element is full line volts. each element (volts to neutral) is e = E/1.73. Current thru each
Current thru each element is i = E/R. element is same as each line wire.
WIRING HEATER ELEMENT VALUES (formulas and symbols)
CONFIGURATION VOLTS (e) AMPS (i) WATTS (W) RESISTANCE (R)
line volts (E)
Parallel line volts (E) E x i E/i
element Ohms (Rn)
line volts (E)
Series line amps (I) e x i e/i
# of elements
line amps (I)
Delta line volts (E) e x i E/i and E/1.73 I
1.73
Star (Wye) E/1.73 line amps (I) e x i and E x I/1.73 e x i and E/1.73 I
Heater Control Voltage Heater Control Voltage Heater Input
Temperature Input Temperature Input Input Temperature Input Power
Control Device Power Control Device Coil Power Control Device Coil
Heater
Contactor
Contactor
Heater
SINGLE PHASE - Load power SINGLE PHASE - Load power 3 PHASE - Load power
thru a temperature controller. thru an external contactor. thru an external contactor.
PLASTIC PROCESS EQUIPMENT, INC. www.ppe.com
e-mail: sales@ppe.com
E 8303 CORPORATE PARK DRIVE W 6385 MONTESSOURI STREET
A MACEDONIA, OHIO 44056-2300 E LAS VEGAS, NEVADA 89113-1186 Toll Free: USA, Canada & Mexico
S 216-367-7000 • FAX: 216-367-7022 S 702-433-6385 • FAX: 702-433-6388 800-362-0706
T TOLL FREE: 800-321-0562 T TOLL FREE: 800-258-8877 Order Fax: 800-223-8305
951