1/16 DIN TEMPERATURE CONTROL


                                 SPECIFICATIONS & PRICES


         Panel Cutout: 1.771" (45mm) sq.
                                        4.654"                   Linear Input: Type L1 to L6 (Refer to Ordering Codes)
                  2.100"               (118.2mm)
                 (53.3mm)  0.717"         3.937"                 Engineering Units     Scalable, -1999 to 9999
                         (8.21mm)        (100mm)                 Digital Filtering     0.1, 1.0, or 10 sec
                                                                 Decimal Position      Selectable, none, 1/10 or 1/100
          2.100"                                      1.750"
         (53.3mm)                                    (44.5mm)
                                                                 Control Characteristics
                                                                 Setpoint Limits  Limited to configured range of TC and RTD
                                                                 Alarms         Adjustable for high/low; selectable process
         Available Inputs                                                       or deviation
         Thermocouple   K, J, N, R, T, S                         Rate           0 to 900 sec
                        Maximum lead resistance, 100 ohms for    Reset          0 to 3600 sec
                        rated accuracy                           Cycle Time     0.2 to 120 sec
         RTD            Platinum, 3-wire, 100 ohms at 0°C, DIN   Gain           0 to 400
                        curve standard (0.00385)                 Gain Ratio     0 to 2.0 (in 0.1 increments)
         Linear         Current and voltage (refer to ordering note)  Control Hysteresis 1 to 100 (on/off configuration)
                                                                 Spread (Output 2) 0 to 100 (above setpoint)
                                                                 Ramp to Setpoint 1 to 100 minutes
         Output Options                                          Autotune       Operator-initiated from front panel
         #1 reverse-acting, #2 direct-acting                     Manual Control  Operator-initiated from front panel
         B & Y          Relay 5 A @ 120 Vac  3 A @ 240 Vac
         F              4-20 mA, 500 ohms max
         S              20 Vdc pulsed                            General
         T              Solid-state relay, 120/240 Vac, zero voltage  Line Voltage   115 to 230 Vac ±10%, 50/60 Hz
                        switched, 1A continuous, 10A surge @ 25°C                    115 to 300 Vdc ±10%, (auto polarity)
                        (use a RC snubber when driving a         Display             Dual, 4-digit, 9.2mm
                        mechanical or mercury relay)                                 Process: orange
         Alarms         Solid-state relay 1 A, 120/240 Vac @ 25°C                    Menu/parameter: green
                        Relay 5 A @ 120 Vac  3 A @ 240 Vac       Power Consumption   Less than 6 VA (instrument)
                                                                 Weight              < 8 oz (227 g)
                                                                 Front Panel Rating  NEMA 4X
         Performance                                             Operating Temperature 32 to 131°F (0 to 55°C)
         Accuracy              ±0.2% of FS, ± one digit          Humidity Tolerance  90% R.H. maximum, non-condensing
         Setpoint Resolution   1 count/0.1 count                 Memory Protection   Solid-state, nonvolatile memory
         Repeatability         ±1.0 count                        Connections         Input and output via barrier strip,
         Temperature Stability  5µ V/°C maximum                                      with locking terminals
         TC Cold End Tracing   0.05°C/°C ambient                 Contacts            Twin bifurcated, double-wipe
         Noise Rejection       Common mode > 70 dB
                               Series mode > 70 dB
         Process Sampling      10 Hz (100 ms)                       16-




            Input     Range   Code    Output 1           Output 2            Options     Price     Options     Price
           "K" TC   0 to 2460°F  KF  Configuration  Price  Configuration  Price
           "K" TC   -18 to 1349°C  KC                                    00=None          N/C  Process Value Retransmit
                                       Code               Code
            "J" TC  0 to 1400°F  JF                                      Dual Alarms           60=4 to 20 mA
                                    0=None             0=None       N/C  10=Dual S.S. Relay (N.O.)  61=1 to 5Vdc  $75.00
            "J" TC  -18 to 760°C  JC  S=Pulsed 20 Vdc  N/C  B=Relay
           "N" TC   0 to 2370°F  NF                    S=Pulsed 20 Vdc  $25.00  20=FloatingTransistor  $40.00  62=0 to 20 mA
                                    B=Relay                                   Open Collector Switch  63=0 to 5 Vdc
           "N" TC   -18 to 1299°C  NC           $25.00  T=S.S. Relay
                                    T=S.S. Relay                         21=24 Vdc drive       Heater Break*
           "R" TC   0 to 3200°F  RF                    E=0-20 mA                                               Consult
                                    E=0-20 mA          F=4-20 mA   $30.00  23=Single Relay     71=10 to 60 A   Factory
           "R" TC   -18 to 1760°C  RC           $30.00
                                    F=4-20 mA          Y=Relay (N.C.)    Communications
           "T" TC   -200 to 601°F  TF                                                         *Requires Current Transformer
                                                                         30=RS-232       $95.00  #580E023U01.....................................$56.00
           "T" TC   -129 to 316°C  TC
                                                                         31=RS-485
           "S" TC   0 to 3200°F  SF                                      Remote Setpoint
           "S" TC   -18 to 1760°C  SC                                    Select (w/alarm)
          100 ohm RTD  -328 to 1562°F  PF                                40=Switch Close  $75.00
          100 ohm RTD  -200 to 850°C  PC       BASE PRICE                41=Switch Open
          100 ohm RTD  -199.8 to 449.9°F  DF                             42=5 volt Input
                                             $ 230.        00            Transducer Excitation
          100 ohm RTD  -128.8 to 232.2°C  DC
                                                                         50=10 Vdc
                                                                         51=12 Vdc       $75.00   U L
                                                                                                 ®
                                                                         52=15 Vdc
                                                                         53=  5 Vdc
                  PLASTIC PROCESS EQUIPMENT, INC.                                            www.ppe.com
                                                                                            e-mail: sales@ppe.com
                   E 8303 CORPORATE PARK DRIVE         W  6385 MONTESSOURI STREET
                  A MACEDONIA, OHIO 44056-2300         E  LAS VEGAS, NEVADA 89113-1186  Toll Free: USA, Canada & Mexico
                   S 216-367-7000 • FAX: 216-367-7022  S  702-433-6385 • FAX: 702-433-6388  800-362-0706
                   T TOLL FREE: 800-321-0562            T  TOLL FREE: 800-258-8877         Order Fax: 800-223-8305
                                                                                                                 767
   762   763   764   765   766   767   768   769   770   771   772