FUJI PXF SERIES ISO-9001
MANUFACTURED IN A
QUALITY SYSTEM CERTIFIED
SPECIFICATIONS FACILITY.
C
RECOGNIZED RECOGNIZED
General Specifications Control Parameters
Power supply voltage 100 V (-15%) to 240 V (+10%) AC, 50/60 Hz, 24 V AC/DC (±10%) Proportional Band (P) 0.1% to 999.9%
Model 100 to 240 V AC 24 V DC/AC Integration Time (I) 0 to 3200 s (invalidated when I = 0)
Power Consumption PXF4 10 VA MAX. 5 VA MAX. Differential Time (D) 0.0 to 999.9 s (invalidated when D = 0)
PXF5 & PXF 13 VA MAX. 8 VA MAX. Control Cycle 100 to 900 ms (in 100 ms), 1 to 99 s (in seconds)
Insulation Resistance 20M Ohms or more (at 500 V DC) Anti-reset Windup 0 to 100% of measurement range
Power source <—> all terminals: 1500 V AC for 1 min Hysteresis Band 50% of measurement range (at 2-position control only)
Withstand Voltage Relay contact output . all terminals: 1500 V AC for 1 min 8: Changed by any of parameter setting, digital input, communication, user
Number of SV and PID Patterns
Between others: 500 V AC for 1 min function keying, zone change.
Process Value Input Control Mode
Auto/Manual/Remote (During 2-position control in Manual mode,
Number of Inputs 1 Mode
Input Setting Programmable scale 2-position manual operation with MV = 100% or 0% is operated.)
• Auto <—> Manual: Balanceless . bumpless
• Thermocouple input: either ±1°C ±1 digit or ±0.3% of indicated
Mode Changeover: • Auto/Manual —> Remote: Balance . bumpless
value ±1 digit, whichever is larger
*except: • Auto/Manual <— Remote: Balance . bumpless
Thermocouple B: 0 to 400°C: no accuracy assurance Alarm
Indication Accuracy Thermocouple R: 0 to 500°C: ±3°C ±1 digit Number of Alarm Up to 5 (depends on the number of DO)
(at Ta = 23°C) Thermocouples of which measuring range is between -200°C and Process value (upper limit/lower limit, absolute/deviation, range), main unit
Alarm Type
-100°C: ±2°C ±1 digit error, etc.(non-excitation, delay, latch, timer function option provided)
• RTD input: ±0.8°C ±1 digit or ±0.2% of indication value ±1 digit, Heater Current Alarm Function Current transformer (CT) is to be prepared separately (see page 10.)
(option)
whichever is larger
Detectable Range 1 A to 100 A
• mV input, voltage input, current input: ±0.3%FS ±1 digit
Detected Current Resolution 0.1A
Temperature Effect on Sensitivity ±0.3%FS/10°C
Setting Resolution 0.1A
• Thermocouple, mV input: 1M Ohms or more
Hysteresis 0.0 to 100.0 A
Input Impedance • Current input: 150 Ohms or less (built-in diode)
• Voltage input: About 1M Ohms Current Transformer (CT) Input (option)
Variation by Signal Source • Thermocouple, mV input: ±0.3%FS ±1 digit per 100 Ohms Single phase CT, 1 point
Resistance • Voltage input: ±0.3%FS ±1 digit per 500 Ohms Input type For 1 A to 30 A: CTL-6-S-H
Allowable Wiring Resistance • RTD: 10 Ohms MAX. (per wire) For 20 A to 100 A: CTL-12-S36-8
• DC voltage input: within ±35 V Range of Detected Current 1 A to 100A
Allowable Input Voltage • Current input: within ±25 mA Detected Current Accuracy Setpoint ±5%FS
• Thermocouple, RTD, mV input: within ±5 V Detected Current Resolution 0.1A
Normal mode: 40 dB (50/60 Hz) ON Time Necessary for Detection 300 ms MIN.
Noise Reduction Ratio Common mode: 120 dB (50/60 Hz) Display and Keys
Between input and power supply: ±1°C at 220 V AC, 50/60 Hz Type LCD (with backlight)
(a) User adjustment: ±50%FS for each of zero and span point
Process value indication: 11-segment, 4-digit [white]
(b) Process value shift: ±10%FS
Input Correction Indication Contents Setpoint indication: 11-segment, 4-digit [green]
(c) Input filter: 0.0 to 120.0 s (filter is off when set to 0.0)
Screen No. indication: 7-segment, 4-digit [orange]
(d) Square root extraction: -0.1 to 105% (OFF if set to -0.1%) Status indication: 42 indicator lamps
Out of the range between -5% and 105% FS (accuracy is not assured Luminance Setting possible (4 steps)
between -5 and 0, and between 100 and 105%FS)
Additional Function Scaling function
*except:
Overrange · Underrange Customizable Function and Program (ramp/soak) Function
• Pt (-200°C to 850°C) input: Out of the range between
64 steps × 1 pattern, 32 steps × 2 patterns, 16 steps × 4 patterns,
• 0 to 10 V DC input: -2% to 105% of FS Number of Program Steps:
• Thermocouple E: Out of the range between -5 to 102% of FS or 8 steps × 8 patterns (1 step = 2 segments)
Control by digital input
Control Output Control Option Status output by digital output
2. Relay contact output (SPDT) 1. Segment time can be set in "Hour, Minutes" or "Minutes, Seconds"
• Proportional cycle: 1 to 150 s 2. Guarantee soak
• Contact structure: 1 SPDT contact *SPDT: single pole double t row 3. Repeat action
Basic Functions
• Contact capacity: 250 V AC/30 V DC, 5A (resistive load) 4. PV start
• Mechanical life: 50 million operations MIN. (100 operations/min) 5. Delay start
• Electrical life: 100,000 operations MIN. (rated load) 6. Power restoring function
3. SSR/SSC drive output Memory Backup EEPROM
• Proportional cycle: 1 to 150 s Operation and Storage Conditions
• ON voltage: 12 V DC (between 10.7 and 13.2 V DC)
Operating Temperature -10°C to 50°C
• OFF voltage: 0.5 V DC or lower
Storage Temperature -20°C to 60°C
• Maximum current: 20 mA DC
Operating/Storage Humidity 90%RH or less (Non condensation)
• Load resistance: 600 Ohms MIN.
Type 4. Current output (0 to 20 mA DC/4 to 20 mA DC) Enclosure
Select among 2 to 6
• Accuracy: ±5%FS Installation Panel mount
• Load resistance: 500 Ohms MAX. External Terminals Screw terminals, M3
5. Voltage output (0 to 5 V DC/1 to 5 V DC/0 to 10 V DC/2 to 10 V DC) • Material: ABS, PPO
• Accuracy: ±5%FS Case • Non-combustibility grade: UL94V-0 equivalent
• Load resistance: 10k Ohms MIN. • Color: Black
6. Motorized valve control output • Panel front side: IP66, NEMA-4X equivalent (When the panel is mounted
• Contact structure: 2 SPST contacts without interlock circuit using our genuine packing. Not water-proof if mounted closely together.)
Protection Structure
*SPST: Single Pole Single Throw • Body: IP20 equivalent (slits on top and bottom)
• Contact capacity: 250 V AC/30 V DC, 3A (resistive load) • Terminals: IP00 equivalent. Terminal cover can be mounted optionally.
• Minimum ON/OFF current: 100 mA (24 V DC) Weight PXF4: approx. 100 g, PXF5: approx. 170 g, PXF9: approx. 220 g
• Mechanical life: 20 million operations MIN. (100 operations/min)
• Electrical life: 100,000 operations MIN. (rated load)
PLASTIC PROCESS EQUIPMENT, INC. www.ppe.com
e-mail: sales@ppe.com
E 8303 CORPORATE PARK DRIVE W 6385 MONTESSOURI STREET
A MACEDONIA, OHIO 44056-2300 E LAS VEGAS, NEVADA 89113-1186 Toll Free: USA, Canada & Mexico
S 216-367-7000 • FAX: 216-367-7022 S 702-433-6385 • FAX: 702-433-6388 800-362-0706
T TOLL FREE: 800-321-0562 T TOLL FREE: 800-258-8877 Order Fax: 800-223-8305
763